PowerBullet

PowerBullet™ - Power / Energy Transducers
Line Powered 100/115/208/230V or 277/347/480/600V
AC Demand and Consumption Measurement
The PowerBullet™ comes as a power or energy transducer designed for monitoring demand and consumption in residential, commercial and industrial applications. It is a line-powered, phase-to-phase unit with outputs compatible with the Voltage or Pulse inputs of most measurement systems. The transducer outputs are directly proportional to kW/kVA for demand and kWh/kVAh for consumption. It takes into account Power Factor and True RMS Values and includes built-in Arc Flash protection.
More Information
Applications
- Equipment Level Optimization - motors, compressed air and cooling compressors
- Branch Circuit Mixed Load Types - lighting and computer equipment
Power Demand Models
- kW and kVA – proportional voltage outputs (compatible with standard 5VDC Analog Inputs)
- PF (Cos phi) and kVAR for Energy Audits – Calculated from resultant data (compound line)
- Peak Demand – Resolution down to 1sec logging interval
(Power Demand models are compatible with SmartReader 3 and SmartReader Plus 3 data loggers.)
Energy Consumption Models
- kW and kWh – Pulse accumulation outputs (compatible with 5VDC Counter Inputs)
- Mixed and Balanced Load Types – Use where submetering does not exist
- Revenue Grade Measurement – High accuracy over 15min logging interval
(Energy Consumption models are compatible with SmartReader 9 and SmartReader Plus 9 data loggers.)
The PowerBullet uses a miniature Rogowski flexible split-core current transducer which makes it small enough to fit inside disconnect enclosures, breaker panels or distribution boxes. Wide Mouth Alligator clips make it easy to connect to the line voltage terminals without tools.
General Specifications
Size
140 x 57 x 57 mm (5.5 x 2.3 x 2.3 in)
Weight
300 grams (11.2 ounces)
Case Material
ABS Plastic UL94V-0
Fuse
0.5A Fast-Acting 100kAAC
Resolution
20W, 20VA or 1pulse/Wh, VAh
Safety Rating
300V Cat IV or 600V Cat III
Voltage Range
90-300VAC or 250-630VAC
Current Range
2-500A (at 600VAC)
Probe OD
51mm (2.0in) Nominal
Measurement Mode
Delta Sigma / True RMS
Operating Limits
10°C to 55°C (14°F to 131°F)
Power Consumption
2.5W 40VA
Software Version
TrendReader 2.39 or Later
Environmental
10 to 90% RH Non-condensing
Maximum Altitude
2000m (6560ft)
Pollution Degree
2 (Non-conductive Dust)
Channel Accuracy
| Measurement | ±0.1% (Before & After Ratio) |
|---|---|
| Transducer | ±0.5% (±3% Position) |
| System | ±1% (±4.5% Position) |
| Demand Output | 98mV FS into 400Ω load |
| 4.99V FS into 10MΩ load | |
| Consumption Output | 5V 6mS Pulse (14% Demand Ripple) |
PowerBullet requires TrendReader 2 version 2.39 or above. If you are using a version of TrendReader 2 prior to version 2.39, click here to download and install the free update.